An overview of the earthing system

Topics covered

  1. Firmly grounded system
  2. Resistance Grounded System
  3. Reason for resistance to earthing
  4. Grounding system at the EHV level

Firmly grounded system

Suppose Phase R is shorted to ground that:

  • Si = Current on short-circuited path ( Fault current )
  • In = Current flowing through the neutral connection to earth
  • Ice = Capacitive current returned via the Phase-2 network ( Phase Y ) – capacitors
  • IcB = Capacitive current returned via the Phase-1 network ( Phase B ) – capacitors

We can write:

Si = In + IcY + IcB + Ir 

Where Ir = Current returned by the network insulation resistance which is always negligible

In the event of LV, the system voltage available between phase and earth is 415 / 1.732 = 240V . The resistance of the earth plate, earth connections, etc.… is of the order of 1.5 Ohms so that the earth current is limited to approximately 240 / 1.5 = 160 amps . This magnitude is not very high and no intentional impedance is needed in a neutral connection to earth.

As in -08 equation because if you can see that if Glossy and ICB is negligible as If = What is the case in the BT system . At 415V the level capacitive earth currents are not significant and therefore we can write:

Substation-Earthing-System
Substation-Earthing-System

Si = In for solidly earthed LV system // equation-09

Resistance earthing System

In the case of an MV system ( 3.3 kV to 33 kV ) the voltage between phase and earth is high. Also capacitive load current is not large enough to compensate for the same, so the earth fault current may be excessive.

Therefore, the resistor is connected between neutral and earth. The current to neutral is limited to 100-400 amps .

Limitation of earth fault / neutral current

Although all MV level power system components are rated at full MV system fault level , for example:

  • Transformer winding,
  • Cables,
  • Bus ducts,
  • Machine rotation, etc.

What is protected by limiting the earth fault current / the current through the neutral?

The neutral of the transformer or generator are earthed by the impedance, the main element of which is resistance. This method is used when the earth current is too high if it is not restricted (for example) by MV generators. Here, a resistor is intentionally connected between neutral and earth. This is to limit the earth fault current.

Reasons to limit the earth current

The reasons for limiting the earth fault current are:

1. In rotating electrical machines like motors and generators, if the earth fault current is high, such as in the case of continuous earthing, the damage to the core would be great. To limit damage to the core, machine manufacturers only allow a limited earth fault current.

This is given in the form of a heart damage curve.

2. A typical value would be 25A-100A for 1 second . This value serves as a guide for selecting NGR and setting stator earth fault relays in generator protection.

3. Damage to windings in rotating electrical machines is not a serious problem (although windings are classified for the full fault level). Winding damage repairs can be done by the local winder. However, in the event of damage to the heart, repairs cannot be made on site. The machine must be returned to the manufacturer for repair, resulting in prolonged production losses.

Since rotating electrical machines are not present at voltage levels above 22 kV, these systems are usually solidly fused .

4. System X0 / X1 ratio also decides the type of neutral earthing. If the corresponding X0 / X1 ratio is within this predefined range. It is a choice between weatherproofing to cope with higher voltage or higher current in case of short circuit. Effectively earthing reduces the overvoltage limit of healthy phases while another phase is short-circuited to earth. But the earth fault current is very high.

This means that the system will need a large capacity circuit breaker, but the isolation system will need to have a moderate BIL rating.

But as the neutral impedance to earth increases, the earth fault current decreases, but the surge factor even increases up to 1.73 times! This therefore requires a circuit breaker with a low current capacity but a HIGH BIL for any insulation system.

Suppose Phase R ( Phase 1 in Figure 4 ) is shorted to ground that:

  • Si = Current on short-circuited path ( Fault current )
  • In = Current flowing through the neutral connection to earthing system
  • Ice = Capacitive current returned via the Phase-2 network ( Phase Y ) – capacitors
  • IcB = Capacitive current returned via the Phase-3 network ( Phase B ) – capacitors

By repeating Equation 8, we can write:

Si = In + IcY + IcB + Ir

Ignore Ir and replace it with the following:

In = -V1 / Rn ( The negative sign indicates that the capacitive charge and discharge current is in phase opposition with the current flowing through neutral )

IcY + IcB = Total capacitive load and healthy phase discharge current = j3CwV1 from equation-07

The representation of the phasor diagram will be:

So, finally, after substituting the expression In and IcY + IcB for the earth fault current in the MV system, we obtain:

If = -V1 / Rn + j3CwV1 // equation -10

The magnitude of the earth fault current will be:

| If | = | V1 | √ (I / Rn) 2+ 9C2w2

Grounding the system at EHV level

In case of HV system ( above 33kV ) the capacitive earth current is large enough to neutralize earth fault currents therefore no resistance is required in the neutral earth connection.

Strong foundations are universally adopted for the following reasons:

1. As we already understood that it is a choice between the weather conditions to deal with higher voltage or higher current in case of short circuit. At EHV level, if we go for a higher voltage than due to the high cost of insulation, selecting a higher voltage will not be a viable idea.

It is better to go for a higher current by choosing a solid ground.

2. The rotating machines are not present in the EHV system. It is therefore not useful to limit the earth fault current as in the MV system. Even though rotating machines are present due to higher voltage, the capacitive earth current is also large enough to neutralize the earth fault current.

Leave a Comment

Your email address will not be published. Required fields are marked *

50% OFF ON ALL COURSES till 15 May 2022
This is default text for notification bar

of escort çukurova escort kozan escort seyhan escort yüreğir escort adana mutlu son masaj besni escort kahta escort gölbaşı escort adıyaman mutlu son masaj bolvadin escort dinar escort sandıklı escort emirdağ escort afyon mutlu son masaj diyadin escort doğubayazıt escort patnos escort ağrı mutlu son masaj ortaköy escort aksaray mutlu son masaj merzifon escort suluova escort taşova escort amasya mutlu son masaj çankaya escort keçiören escort yenimahalle escort mamak escort etimesgut escort sincan escort altındağ escort pursaklar escort gölbaşı escort polatlı escort çubuk escort kahramankazan escort beypazari escort ankara mutlu son masaj alanya escort manavgat escort serik escort antalya mutlu son masaj şehitkamil escort nizip escort ıslahiye escort antep mutlu son masaj ardahan mutlu son masaj artvin mutlu son masaj hopa escort borçka escort aydın mutlu son masaj efeler escort nazilli escort kuşadası escort söke escort didim escort incirliova escort çine escort germencik escort balıkesir mutlu son masaj karesi escort altıeylül escort edremit escort bandırma escort gönen escort ayvalık escort burhaniye escort bigadiç escort susurluk escort bartın mutlu son masaj batman mutlu son masaj kozluk escort sason escort beşiri escort bayburt mutlu son masaj bilecik mutlu son masaj bozuyuk escort bingöl mutlu son masaj solhan escort genç escort karlıova escort bitlis mutlu son masaj tatvan escort güroaymak escort ahlat escort bolu mutlu son masaj gerede escort burdur mutlu son masaj bucak escort bursa mutlu son masaj osmangazi escort yıldırım escort nilüfer escort inegöl escort gemlik escort mudanya escort mustafakemalpaşa escort gürsu escort karacabey escort orhangazi escort kestel escort iznik escort çanakkale mutlu son masaj biga escort can escort gelibolu escort ayvacık escort çankırı mutlu son masaj çerkes escort çorum mutlu son masaj sungurlu escort osmancık escort alaca escort iskilip escort denizli mutlu son masaj pamukkale escort merkezefendi escort çivril escort acıpayam escort tavas escort diyarbakır mutlu son masaj kayapınar escort bağlar escort yenişehir escort ergani escort bismil escort sur escort silvan escort çermik escort dicle escort düzce mutlu son masaj akçakoca escort kaynaşlı escort edirne mutlu son masaj keşan escort uzunköprü escort ipsala escort elazığ mutlu son masaj kovancılar escort karakoçan escort erzincan mutlu son masaj erzurum mutlu son masaj yakutiye escort palandöken escort aziziye escort horasan escort oltu escort pasinler escort odunpazarı escort tepebaşı escort eskişehir mutlu son masaj bulancak escort espiye escort tirebolu escort görele escort giresun mutlu son masaj gümüşhane mutlu son masaj kelkit escort hakkari mutlu son masaj yüksekova escort şemdinli escort hatay mutlu son masaj antakya escort iskenderun escort defne escort dörtyol escort samandağ escort kırıkhan escort reyhanlı escort arsuz escort altınözü escort hassa escort payas escort erzin escort yayladağı escort ığdır mutlu son masaj yalvaç escort eğirdir escort sarkıkaraağaç escort ısparta mutlu son masaj istanbul mutlu son masaj izmir mutlu son masaj buca escort karabağlar escort bornova escort karşıyaka escort konak escort bayraklı escort çiğli escort torbalı escort menemen escort gaziemir escort ödemiş escort kemalpaşa escort bergama escort menderes escort aliağa escort tire escort