Automatic Transfer System (ATS) explained in detail

The role of the automatic transfer system

The fundamental role of the automatic transfer system can now be defined using the basic elements of utility power, system topology, on-site generation, and uninterruptible power supplies.

Operational requirements of the automatic transfer system (photo credit: bernini-design.com)

In this role, the automatic transfer system must display the following characteristics:

  1. Robustness – it should perform as intended, even under abnormal power system conditions, without human intervention. Equally important, he must be able to distinguish when a system condition does not warrant transfer to an AC power source.
  2. It must be able to control the switchboard as needed and, in addition, must be able to transmit the appropriate signals to the emergency power source, if necessary (for example, to signal a generator when to start.

Simply put, the role of the automatic transfer system is to provide the automatic transfer of power for its associated load group from a normal power source , such as a utility, to an alternate power source, such as back-up generation, in the event of failure of the normal source.

Example of system description

To fully illustrate the operational requirements of a typical automatic transfer system, a more detailed representation of the system is required. For this purpose, the main-main topology used is used, but with the details of the automatic transfer system shown:

In Figure 1, the automatic transfer logic makes it possible to decide which automatic operations should take place and when. It controls the operation of the two transfer circuit breakers, CB-UM and CB-GM, and receives status inputs from these circuit breakers. It can also initiate generator start-up for the AC power source.

Undervoltage (device 27) and reverse voltage (device 47) relays on each power source indicate the transfer logic of their state . In addition, a frequency relay (device 81) is present to indicate the frequency of the
AC power source.

Voltage transformers, or VTs, advance the voltage system to instrumentation levels usable by these relays. A user interface is used to adjust certain operating parameters of the system and to update the user on the status of the system.

Using this example system, the operational requirements of a typical automatic transfer system will be examined.

(ATS)

Operating modes

An essential requirement of any automatic transfer system is the possibility of having different modes of operation . In a given mode of operation, the transfer system will respond in a given way to changing system conditions. For a different mode of operation, the transfer system will respond differently.

The two basic operating modes that any automatic transfer system must have are:

  1. Manual mode
  2. Automatic mode

In manual mode , the automatic transfer system does not operate any automatic operation, that is, it does not respond to the changing conditions of the system. All circuit breaker operations must be performed manually. Conversely, in automatic operating mode, all operations, with a few exceptions, are automatic and the system will respond automatically to changes in system conditions.

On the surface it seems like a simple arrangement, and to some extent it is true.

</ p>

Good ATS design

However, a good design of the automatic transfer system has well thought out mode logic that answers the following questions:

  1. Can the system be put into automatic mode if the system conditions are not correct (for example, if an automatically operated circuit breaker is in the withdrawn position or if it is not present in the circuit breaker cubicle)?
  2. What manual operations are authorized in automatic mode (for example, manual opening of circuit breakers)?
  3. What happens if an authorized manual operation is performed on an automatically controlled device (for example, if an automatically controlled circuit breaker is manually tripped or trips due to a fault)?

Such questions are not always easy to answer. In fact, they require, in a well-designed automatic transfer system, the inclusion of a third mode of operation, generally referred to as automatic mode failure .

The three operating modes then generally work as follows:

  1. Manual mode
  2. Automatic mode
  3. Auto mode failed

1. Manual mode

Selected via a selector position or other predetermined user input through the user interface. No automatic operation occurs.

2. Automatic mode

Selected via a selector position or other predetermined user input through the user interface. Attempting to enter automatic mode if the system conditions are not correct, the system is in automatic mode failure mode. .

In automatic mode, operations for certain circuits The circuit breakers (such as the main and secondary circuit breakers) are automatic. However, manual tripping (or tripping due to a fault) of automatically controlled circuit breakers is authorized. Such manual or error-triggered operations will cause the system to enter auto mode failure mode.

3. Auto mode failed

No automatic operation occurs. For automatically controlled circuit breakers, only manual tripping (or tripping due to a fault) is authorized. To exit this operating mode, the system must be placed in manual mode.

This arrangement provides a high level of security for the handover scheme , i.e. unwanted or “annoying” operations are minimized, which improves the security, maintainability and reliability of the system.

Of necessity, to make this arrangement mode logical to function properly, the circuit breaker state must consist of both an open-closed indication and, for withdrawable circuit breakers, a circuit breaker cubicle switch indication.

Circuit breaker cubicle switches are a feature that should not be overlooked as they are essential for the proper functioning of an automatic transfer system with withdrawable circuit breakers. For the same reason, overcurrent switches for low voltage circuit breakers or latching relays for medium voltage circuit breakers are also required.

Another question that frequently arises is that of a “test” mode of operation. While this can be made into a separate mode of operation, this is usually handled more appropriately via voltage failure simulation test switches when the system is in automatic mode.

Leave a Comment

Your email address will not be published. Required fields are marked *

50% OFF ON ALL COURSES till 15 May 2022
This is default text for notification bar

of escort çukurova escort kozan escort seyhan escort yüreğir escort adana mutlu son masaj besni escort kahta escort gölbaşı escort adıyaman mutlu son masaj bolvadin escort dinar escort sandıklı escort emirdağ escort afyon mutlu son masaj diyadin escort doğubayazıt escort patnos escort ağrı mutlu son masaj ortaköy escort aksaray mutlu son masaj merzifon escort suluova escort taşova escort amasya mutlu son masaj çankaya escort keçiören escort yenimahalle escort mamak escort etimesgut escort sincan escort altındağ escort pursaklar escort gölbaşı escort polatlı escort çubuk escort kahramankazan escort beypazari escort ankara mutlu son masaj alanya escort manavgat escort serik escort antalya mutlu son masaj şehitkamil escort nizip escort ıslahiye escort antep mutlu son masaj ardahan mutlu son masaj artvin mutlu son masaj hopa escort borçka escort aydın mutlu son masaj efeler escort nazilli escort kuşadası escort söke escort didim escort incirliova escort çine escort germencik escort balıkesir mutlu son masaj karesi escort altıeylül escort edremit escort bandırma escort gönen escort ayvalık escort burhaniye escort bigadiç escort susurluk escort bartın mutlu son masaj batman mutlu son masaj kozluk escort sason escort beşiri escort bayburt mutlu son masaj bilecik mutlu son masaj bozuyuk escort bingöl mutlu son masaj solhan escort genç escort karlıova escort bitlis mutlu son masaj tatvan escort güroaymak escort ahlat escort bolu mutlu son masaj gerede escort burdur mutlu son masaj bucak escort bursa mutlu son masaj osmangazi escort yıldırım escort nilüfer escort inegöl escort gemlik escort mudanya escort mustafakemalpaşa escort gürsu escort karacabey escort orhangazi escort kestel escort iznik escort çanakkale mutlu son masaj biga escort can escort gelibolu escort ayvacık escort çankırı mutlu son masaj çerkes escort çorum mutlu son masaj sungurlu escort osmancık escort alaca escort iskilip escort denizli mutlu son masaj pamukkale escort merkezefendi escort çivril escort acıpayam escort tavas escort diyarbakır mutlu son masaj kayapınar escort bağlar escort yenişehir escort ergani escort bismil escort sur escort silvan escort çermik escort dicle escort düzce mutlu son masaj akçakoca escort kaynaşlı escort edirne mutlu son masaj keşan escort uzunköprü escort ipsala escort elazığ mutlu son masaj kovancılar escort karakoçan escort erzincan mutlu son masaj erzurum mutlu son masaj yakutiye escort palandöken escort aziziye escort horasan escort oltu escort pasinler escort odunpazarı escort tepebaşı escort eskişehir mutlu son masaj bulancak escort espiye escort tirebolu escort görele escort giresun mutlu son masaj gümüşhane mutlu son masaj kelkit escort hakkari mutlu son masaj yüksekova escort şemdinli escort hatay mutlu son masaj antakya escort iskenderun escort defne escort dörtyol escort samandağ escort kırıkhan escort reyhanlı escort arsuz escort altınözü escort hassa escort payas escort erzin escort yayladağı escort ığdır mutlu son masaj yalvaç escort eğirdir escort sarkıkaraağaç escort ısparta mutlu son masaj istanbul mutlu son masaj izmir mutlu son masaj buca escort karabağlar escort bornova escort karşıyaka escort konak escort bayraklı escort çiğli escort torbalı escort menemen escort gaziemir escort ödemiş escort kemalpaşa escort bergama escort menderes escort aliağa escort tire escort